PCB Mounted Type Current Transformer, CT Metering
Excellent precision performance
Easy fixing on PCB, saving space for the meters
Strong insulation voltage between the primary and the secondary >4kV/1min
Attractive appearance, casing color is available on request
Big inner hole, suitable for any primary cables and bus bars.
Simple assembly, saving production cost
CT without DC Immunity
Current Transformer, as a current sensing part, has high accuracy, small phase shift, smart size and big measurement range. Comparing with other sensors like shunt, the cost is higher, but it’s more reliable and precise, so they are extensively used in the energy meter, electric devices with overload protection and ground detection as current sensing.
Features
AC measurement capacity is 20% higher than rated current, 480A max.
High Precision, suitable for kwh meter Class 0.2, Class 0.5, Class 1.0, Class 2.0.
Typical AC current measurement error is within 0.02% at lb test point.
Typical phase displacement < 15′, additional compensation is not needed.
Big load capacity, up to 100ohm for 0.1Class CT.
Very reliable and stable performance at different temperature conditions.
Good linearity, it support automatically software calibration.
Different type for different fixing and assembly easily.
Quick connection to PCB available on request.
RoHS Compliance is available on request.
Characteristics
Dielectric Strength between primary and secondary >4kV/1min.
Insulation Resistance between primary and secondary >500MΩ(500VDC)
Phase displacement < 15′, AC current error < ±0.1%.
Load Capacity: 20Ωmax, work frequency: 20Hz~10KHz.
Ambient Temperature: -40℃~+85℃ (-40℃~+115℃ on request).
Relative Humidity:≤95% (25℃) Altitude: ≤10000m.
CT with DC Immunity
Current Transformer with DC immunity has special double-core structure. One core is for AC measurement, the other is for DC. It can accurately measure current from 0.01A to 200A in the meter. DC immunity range is up to 160A. It can serve different types of meters like 40A, 60A, 80A, 100A, 120A, 150A, 200A. Meter accuracy can be up to Class 0.2, Class 0.5, Class 1.0, Class 2.0.
Features
Special double-core structure
AC measurement capacity is 20% higher than rated max current, 250A max.
High Precision, suitable for kwh meter Class 0.2, Class 0.5, Class 1.0, Class 2.0.
Typical meter measurement error with DC influence is within 2.5% for 0.1 Class CT.
Small phase shift, typical phase displacement < 15′ and additional compensation is not needed.
Very reliable and stable performance at different temperature conditions.
Different type for different fixing and assembly easily.
Quick connection to PCB available on request.
RoHS Compliance is available on request.
Characteristics
Dielectric Strength between primary and secondary >4kV/1min.
Insulation Resistance between primary and secondary >500MΩ(500VDC)
Phase displacement < 15′, AC current error < ±0.1%.
Load Capacity: 20Ωmax, work frequency: 50Hz/60Hz.
Ambient Temperature: -40℃~+85℃ (-40℃~+110℃ on request).
Relative Humidity:≤95% (25℃) Altitude: ≤10000m.